TSM4001CP.jpg
TSM4001CP.jpg

Teracom TSM400-1-CP 1-Wire carbon dioxide sensor

Product Code:
TSM400-1-CP
Manufacturer Teracom
Sales price: 203,00 €(Includes 24% VAT)
Sales price without TAX:163,71 €
Product Availability:

Show Shipping Cost:
  • Description
  • Specifications
  • Downloads
  • Reviews
Teracom TSM400-1-CP 1-Wire carbon dioxide sensor

TSM400-1-CP is a multi-parameter sensor that supports the 1-Wire protocol. The sensor measures the concentration of carbon dioxide and atmospheric pressure. Both basic sensor elements, for carbon dioxide and pressure, used in the device are digital. This ensures high measurement accuracy and longterm stability. The basic sensing element for atmospheric pressure is factory calibrated and it does not require any lifetime recalibration. Automatic calibration is available for carbon dioxide measurements. TSH400-1-CP is housed in a slim plastic enclosure. The bottom part of the enclosure is suitable for installation on standard flush-mounted/cavity wall boxes ø68mm, with installation openings on 61mm.

Features:
• LED indicator for status of communication
• Excellent long-term stability
• Firmware update with Teracom controller via the 1-Wire interface

Applications:
• Environmental quality monitoring and assessment for offices
• CO2 pollution monitoring
• Smart ventilation systems

1-Wire carbon dioxide sensor can be used with:
• Temperature and humidity data logger TCW210-TH
• Ethernet IO module TCW241
• Ethernet data logger TCW220
• 4G LTE universal IO module TCG140-4

Warranties - Returns:
Money Return: Repair - Replacement:
20 days 36 months
Specifications
Dimensions 81 x 81 x 30 mm
Weight 66g
Operating temperature range -20 to 60°C
Operating
relative
humidity range
5 to 95%
(non-condensing)
Storage
temperature range
-20 to 60°C
Storage
relative
humidity range
5 to 95%
(non-condensing)
Ingress protection IP20
Input Voltage
(including -15/+20%
according to
IEC 62368-1)
4.5 to 26 VDC
Current consumption 25 mA@5VDC
(Peak: 150mA@5VDC)
CO2 measurements
Range 400 to 5000 ppm
Accuracy ± (40 ppm + 5 %)
Resolution 1 ppm
Calibration Automatic, if the sensor is exposed to fresh air for more than 30 minutes
Pressure measurements
Range 10 to 1200 hPa
Accuracy (min.) ±1.5 (25°C, 750 hPa)
Accuracy (max.) ±2.5 (-20°C to + 85°C, 300 to 1100 hPa)
Resolution 1 hPa
There are yet no reviews for this product.

RELATED PRODUCTS

TERACOM_TCW241.jpg
Teracom TCW241 - Ethernet I/O module
160,00 €
Available
TSC200.jpg
Teracom TSC200 1-Wire current sensor
84,00 €
Available
TERACOM_TCW210_TH.jpg
Teracom TCW210-TH - Temperature and humidity data logger
145,00 €
Available
TCG140_4e.jpg
Teracom TCG140-4e 4G LTE universal IO module
300,00 €
Available

YOU HAVE SEEN RECENTLY

TSM4001CP.jpg
Teracom TSM400-1-CP 1-Wire carbon dioxide sensor
203,00 €
14 Days

INTEREST-FREE INSTALLMENTS BY CREDIT
IN CASH
BANK DEPOSIT
PAYMENT BY

LOGIN